86exporter.com Home       Products Catalog      Suppliers Catalog      Log In        Sign up
      About Us
      Profile
      Products
      Contact Us


Shenzhen Xiaogen Electric Equipment Co.,Ltd

Products >> low frequency UPS,10~200KVA,data management equipm

low frequency UPS,10~200KVA,data management equipm

Build Your Online Product Catalogs?



Description
Product Name: low frequency UPS,10~200KVA,data management equipm
Supply Ability: 4000 pieces/momth
Related proudcts tiny ups,
Specifications GP9330C 10KVA-200KVA
Price Term: FOB,CIF
Port of loading: Shenzhen
Minimum Order 1 piece
Unit Price: USD 1-10000

Low Frequency UPS with 10 to 200kVA Power 3ph In/3ph Out



Applications

Data management equipment and system

Automatic control systems

Hospital

Mini office system

Telecommunication systems

Bank champion UPS, industrial UPS



Key Feature

High reliable

Adopt twin change online technology, sequester extraneous interference

Favorable overload ability and protection

Design with 100% unbalance protection

100% non-linear load ability

IGBT, PWM inverter together with digital

Super safety

The output isolate transformer can avoid the destruction of abnormal signal & lightning stroke

With static bypass, repair bypass, battery maintain bypass

Cold start champion UPS, industrial UPS



Model GP9330C
Capacity 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA 80KVA 100KVA 120KVA 140KVA 160KVA 200KVA
Input Voltage 220/380*(1+/-20%)V AC(3 phases+N+G)
Frequency 50*(1+/-10%)Hz
Power factor 0.8(0.95 if UPS with filter)
Phase 3 phases 4 wires+G
Bypass Voltage 380*(1+/-15%)V AC
Frequency 50*(1+/-2%)Hz
Output Voltage 380*(1+/-1%)V AC (steady state)
Frequency 50*(1+/-5%)Hz(AC power mode); 50*(1+/-0.1%)Hz(battery mode)
Power factor 0.8(lagging)
Wave form Sine wave
Distortion no more than 3%(linear load); no more than 5%(non-linear load)
Transitory voltage of Dvnamic load +/-5%(0 to 100% or 100% to 0 abrupt change)
Transfory recover time less than 10ms(+/-5%)
Unbalance voltage less than 3%(linear load); less than 1%(balanced load)
Overload capacity 150% for 1 min; 125% for 10 min; more than 150% for 200ms
Crest factor 3:1
Efficiency no less than 90%, 95%(ECO mode)
Battery Type 12V DC sealed lead acid battery, maintenance free
Nominal voltage 384V DC(32pcs); 396V DC(33pcs)
Recharge time less than 10 hours up to 90% capacity
Charge current 10~25A(adjustable)
Transfer time 0ms(AC to DC or DC to AC), less than 4ms(Bypass to inverter or inverter to bypass)
LCD display UPS work situation, AC power situation, battery situation, automatic tu

Contact Us
Company: Shenzhen Xiaogen Electric Equipment Co.,Ltd
Contact: Mr. Kevin Huang